Common faults, codes and recommended actions for Ideal Logic, Logic+, Logic Max, Vogue and Independent ranges. Always confirm against the appliance's own fault code sticker or manual, and follow safe isolation procedure before investigation.
F1
Low system water pressure
Re-pressurise via filling loop to approx 1.0–1.5 bar cold; check for leaks and expansion vessel charge if pressure drops repeatedly.
F2 / L2
Flame loss / ignition lockout
Check gas supply and inlet pressure, ignition electrode condition/gap, and condensate trap/pipe for blockage or freezing before resetting.
F3
Fan fault
Check fan wiring/connector, PCB fan output, and flue/terminal for restriction; replace fan if faulty.
F4 / L4
Flow thermistor fault
Check flow NTC sensor resistance against manufacturer chart and wiring continuity; replace if out of range.
F5
Return thermistor fault
Check return NTC sensor resistance and connector; replace if faulty.
F6
Outside sensor failure
Check outdoor sensor wiring and connections (weather compensation models); replace sensor if open/short circuit.
F7
Low mains voltage
Check incoming electrical supply voltage and wiring connections; investigate building supply if voltage is genuinely low.
F9 / L9
Unconfigured or faulty printed circuit board (PCB)
Check PCB configuration/DIP switches per model; reconfigure or replace PCB if fault persists.
L1
Flow temperature overheat lockout / no water flow detected
Check pump operation, system flow, airlocks and open radiator valves; verify flow sensor before resetting.
L3
No flow thermistor fault / loss of water flow
Check pump, system flow rate and blockages; check flow thermistor wiring and resistance.
L5 / LC
Boiler has reset too many times in a short period (repeated lockout cycling)
Not a fault in itself — check fault history/log to find the underlying repeating fault (commonly F1 or L2) and address the root cause.
L6
False flame detection / flame signal fault
Check flame electrode condition, earthing/polarity, and PCB flame detection circuit.
C0
Central heating demand / signal issue
Check room thermostat/programmer wiring, settings and demand signal to the boiler.
C2
Boiler chip card (BCC) fault
Check the boiler chip card is correctly fitted and configured; replace if faulty (System/Regular models).
Status 0
Boiler idle / no current demand — not a fault
Normal standby display; if it persists with no heating/hot water response, check thermostat/programmer demand and wiring.